Description
Output Power Capacity 10 kW / 10 kVA Max Configurable Power 10 kW / 10 kVA Nominal Output Voltage 230V Output Voltage Distortion Less than 3% Output Frequency (sync to mains) 50/60Hz +/- 3 Hz Other Output Voltages 220, 240 Crest Factor 3 : 1 Topology Double Conversion Online Waveform Type Sine wave Output Connections (1) Hard Wire 3-wire (H N + G) (6) IEC 320 C13 IEC 320 C13 (4) IEC 320 C19 IEC 320 C19 (3) IEC Jumpers
-
246.00 lb(s)
-
-
Communication Interface: Ethernet, Serial (RS-232), USB
-
UPS, temperature probe, USB cable, Web/SNMP management card, warranty card, CD with software, documentation CD, installation guide
-
Color: BlackForm Factor: External
-
17″H x 10.35″W x 28.15″D
-
Communications & Management
Interface Port(s): RJ-45 10/100 Base-T, RJ-45 Serial, Smart-Slot, USB
Control panel: Multi-function LCD status and control console
Audible Alarm: Audible and visible alarms prioritized by severity
Emergency Power Off (EPO): Yes
Available SmartSlot Interface Quantity: 1
-
Battery Run Time (max): 3.80 minute(s)Power Provided: 10 kWSurge Suppression: Standard
-
-
Output
Output power capacity: 10.0 KWatts / 10.0 kVA
Max Configurable Power (Watts): 10.0 KWatts / 10.0 kVA
Nominal Output Voltage: 230V
Output Voltage Distortion: Less than 2%
Output Frequency (sync to mains): 50/60Hz +/- 3 Hz
Other Output Voltages: 220, 240
Load Crest Factor: 3 : 1
Topology: Double Conversion Online
Waveform type: Sine wave
Output Connections:
(6) IEC 320 C13 (Battery Backup)
(4) IEC 320 C19 (Battery Backup)
(1) Hard Wire 3-wire (H N + G) (Battery Backup)
(3) IEC Jumpers (Battery Backup)
Bypass: Internal Bypass (Automatic and Manual) -
Input
Nominal Input Voltage: 230V, 400V 3PH
Input frequency: 40 – 70 Hz (auto sensing)
Input Connections: Hard Wire 3 wire (1PH+N+G), Hard Wire 5-wire (3PH + N + G)
Input voltage range for main operations: 160 – 275V
Input voltage adjustable range for mains operation: 100 – 275 (half load), 173 – 476 (half load)V
Other Input Voltages: 220, 240, 380, 415 -
Batteries & Runtime
Battery type: Maintenance-free sealed Lead-Acid battery with suspended electrolyte : leakproof
Typical recharge time: 1.5hour(s)
Replacement Battery: APCRBC140
Expected Battery Life (years): 3 – 5
RBC Quantity: 2
Extendable Run Time: 1 -
Surge Protection
Surge energy rating: 480Joules
Operating Environment: 32 – 104 °F ( 0 – 40 °C )
Operating Relative Humidity: 0 – 95 %
Operating Elevation: 0-10000ft ( 0-3000meters )
Storage Temperature: -15 – 45 °C
Storage Relative Humidity: 0 – 95% non-condensing %
Storage Elevation: 0-50000ft ( 0-15000meters )
Audible noise at 1 meter from surface of unit: 55.0dBA
Online thermal dissipation: 1947.0BTU/hr
Protection Class: IP 20
-
Compliant Standards: CE, EAC, EN 62040-1, EN 62040-2, Energy Star, IEC 62040-1, IEC 62040-2, IP20, IRAM, RCM, REACH, RoHS, VDE