DS60VGPV-1500G/51

 

Part Number: 3956
  • Type 1+2 surge protector for photovoltaic
  • VG technology
  • 1500 Vdc
  • No leakAge, no operating currents
  • Improved life expectancy
  • Iimp : 12,5 kA/pole
  • Common/Differential mode protection
  • Remote signaling
  • UTE C61-740-51, EN 50539-11 compliance

DS60VGPV/51 are type 1+2 heavy duty surge protectors are designed to protect against lightning surge voltages in photovoltaic power supply network. These protectors are recommended when a direct lightning strike is possible on the installation. The DS60VGPV/51 SPDs may withstand up to 12.5 kA 10/350µs, it incorporates CITEL’s exclusive patented ‘VG technology’

Out of stock

Category:

Description

SPD type
follow test IEC 61643-11
1 +2
Network PV network 1250 Vdc
PV Network voltage 1250 Vdc
Max. PV operating voltage 1500 Vdc
Residual Current
Leakage current to Ground
none
PV Permanent Operating current
Current consumption at Ucpv
None
Follow current none
Nominal discharge current
15 x 8/20 µs impulses
20 kA
Max. discharge current
max. withstand @ 8/20 µs by pole
40 kA
Impulse current by pole
max. withstand 10/350µs by pole
12.5 kA
Total lightning current
max. total withstand @ 10/350µs
25 kA
Current withstand short circuit PV 15000 A
Connection mode +/-/PE
Protection mode(s) MC/MD
Protection level
@ In (8/20µs)
3.4 kV
Protection level L/N
@ In (8/20µs)
3.4 kV
Protection level L/PE
@ In (8/20µs)
3.4 kV
Protection level CM/DM
@ In (8/20µs)
4.7/5.4 kV

Photovoltaic surge protection for residential installation

For low power PV applications, i.e. residences and small offi ces, it is necessary to consider surge protecting the AC output of the Inverter that connects directly into the electric power grid as well as the DC input side of the Inverter fed by the PV modules.

PV surge protection for industrial and public building

Medium to large power PV systems can be installed on industrial and service facilities. In order to avoid very costly downtime and lost productivity resulting from a direct or indirect lightning strike, it is critical, and in some cases mandatory, to install surge protection at key points within your facility and its vital power and communication networks.